Skip to main content
Loading…
This section is included in your selections.

International Fire Code Section 6107 is amended by adding the following new subsections:

Sec. 6107.5 Protecting containers from displacement. LP-gas containers greater than or equal to 125-gallons must be anchored or strapped to prevent lateral displacement. Anchors or straps must be an approved, listed device. Methods of securing LP-gas containers 2,000-gallons or greater must be designed by a licensed professional.

Sec. 6107.6 Earthquake shut-off valves. LP-gas containers greater than or equal to 125-gallons must be protected with an approved, listed earthquake shut-off device.

6107.7 Non-compliant installed LP-gas containers. Existing, non-compliant LP-gas containers must be upgraded to comply with sections 6107.5 and 6107.6 when accessory to a building undergoing a change in use or when tank is replaced or modified.

(Ord. 1187-21 § 3, 2021).